|
Accession number;99A0134663
|
| Title;Working situation of gas cogeneration system in new Sapporo Palace Hotel. Introduction case of dual-purpose normal power generating and disaster prevention facilities using city gas only. |
| Author;
TAKAHASHI KENJI
(Hokkaido Gas Co., Ltd.)
|
Journal Title;Kurin Enerugi
|
Journal Code:L1693A
|
ISSN:0918-7510
|
|
VOL.8;NO.1;PAGE.59-65(1999)
|
| Figure&Table&Reference;FIG.9, TBL.1 |
| Pub. Country;Japan |
| Language;Japanese |
| Abstract;The titled hotel with 32 stories above ground and 515 guest rooms which was opened in 1996 set cogeneration facilities with 3 gas engines of the city gas fuel 415kW as a dual-purpose normal power generating and disaster prevention facilities. Steam is generated by a waste heat boiler by engine exhaust gas, the hot water is made by recoverying the heat of the engine cooling water, and the cold heat is obtained by a steam absorption refrigerator. It is operated with the power purchase suppressed so as to feed the 72% of the all electric power load in 1997, cover the 49% of the thermal load, and attain 70% of the average yearly combined efficiency. |
|
|
|
Related Articles;
|