Evaluation of CO2Reduction Measures Using Dynamic Heat Load Model Based on Observed Data at the Office Building.
|
Accession number;01A0595423
|
| Title;Evaluation of CO2Reduction Measures Using Dynamic Heat Load Model Based on Observed Data at the Office Building. |
| Author;
IHARA TOMOHIKO
(Tokyo Univ., Graduate School of Engineering, JPN)
ISHITANI HISASHI
(Tokyo Univ., Graduate School of Engineering, JPN)
MATSUHASHI RYUJI
(Tokyo Univ., Graduate School of Frontier Sci., JPN)
YOSHIDA YOSHIKUNI
(Tokyo Univ., Graduate School of Engineering, JPN)
ROKUGAWA SHUICHI
(Tokyo Univ., Graduate School of Engineering, JPN)
KONDO YOSHINORI
(National Inst. Environmental Studies)
HIGUCHI SHUJI
(Shinryo Corp.)
|
Journal Title;Energy and Resources
|
Journal Code:Z0986A
|
ISSN:0285-0494
|
|
VOL.22;NO.3;PAGE.241-247(2001)
|
| Figure&Table&Reference;FIG.8, TBL.5, REF.9 |
| Pub. Country;Japan |
| Language;Japanese |
| Abstract;An energy demand/supply simulation model by a dynamic thermocapillary load model was verified through the use of air conditioning and meteorological data measured for long period in eco-office in a laboratory in Tsukuba City. Energy amount necessary for removal of a heat capacity from a building is calculated by the calculation model. Results of energy saving and reduction of CO2 emission was calculated by each countermeasures such as photovoltaic power generation, sola r thermal application, warm water heat storage tank, heat insulating materials, total heat exchanger, bilayer sash, etc.The above proved the eco-office reduces the emission 78.5% when compared to the case of taking not countermeasure. |
|
|
|