Accession number;02A0423787
|
| Title;Leakage Current Analysis for Monitoring the Conditions of Polymer Insulators. |
| Author;
KUMAGAI S
(Akita Univ., Akita, Jpn)
YOSHIMURA N
(Akita Univ., Akita, Jpn)
|
Journal Title;Proceedings of the Symposium on Electrical and Electronic Insulating Materials and Applications in Systems
|
Journal Code:G0398B
|
ISSN:
|
|
VOL.33rd;NO.;PAGE.55-58(2001)
|
| Figure&Table&Reference;FIG.6, REF.6 |
| Pub. Country;Japan |
| Language;English |
| Abstract;Leakage current on contaminated polymer insulators was analyzed using digital signal processing techniques. Salt-fog tests with non-soluble deposit were conducted in a laboratory, during which leakage current was separated into conductive, dry-band arc and their transition components. The time-integrated value (cumulative charge) of each component was measured. A prototype of artificial neural network-based system that can estimate hydrophobic states and contamination levels at the surface of polymer insulators by employing leakage current information was constructed. (author abst.) |
|
|
|
Related Articles;
|