Accession number;02A0423801
|
| Title;Interference Analysis and Rejection of Partial Discharge (PD) Monitoring Signal On-site. |
| Author;
WANG X
(Tsinghua Univ., Beijing, Chn)
ZHU D
(Tsinghua Univ., Beijing, Chn)
LI F
(Tsinghua Univ., Beijing, Chn)
|
Journal Title;Proceedings of the Symposium on Electrical and Electronic Insulating Materials and Applications in Systems
|
Journal Code:G0398B
|
ISSN:
|
|
VOL.33rd;NO.;PAGE.111-114(2001)
|
| Figure&Table&Reference;FIG.6, TBL.1, REF.5 |
| Pub. Country;Japan |
| Language;English |
| Abstract;According to the waveform and spectrum characteristics, various interference during on-line PD measurement could be divided into three types such as the sinusoidal continuous noises, pulse shaped interference (including the periodical and stochastical) and background noises (similar to the white noise). Generally speaking, various digital filters could be used to suppress the sinusoidal noise. Some rejection methods for the pulse shaped interference have been developed according to some waveform characteristics and statistical features in the time domain. And the wavelet analysis is a feasible solution to reduce background noises. This paper would make an overall introduction to the anti-interference architecture of a PD monitor and diagnosis system installed at a transformer-generator unit of a power plant in China. The results were also provided in detail about the analysis and rejection for various interference during on-site PD measurement. (author abst.) |
|
|
|
Related Articles;
|